544 Fieldbus control through a fieldbus adapter
Drive parameter
53.03 FBA data out3
53.05 FBA data out5
51.27 FBA A par refresh
19.12 Ext1 control mode
20.01 Ext1 commands
20.02 Ext1 start trigger type
22.11 Speed ref1 source
1)
Read-only or automatically detected/set
2)
Example
The start sequence for the parameter example above is given below.
Control word:
• 477h (1143 decimal) – > READY TO SWITCH ON
• 47Fh (1151 decimal) – > OPERATING (Speed mode)
Setting for ACS880
drives
2)
23.12
2)
23.13
1 =
Refresh
2 =
Speed
12 =
Fieldbus A
1 =
Level
4 =
FB A ref1
Description
Acceleration time 1
Deceleration time 1
Validates the configuration parameter
settings.
Selects speed control as the control
mode 1 for external control location
EXT1.
Selects fieldbus adapter A as the source
of the start and stop commands for
external control location EXT1.
Selects a level-triggered start signal for
external control location EXT1.
Selects fieldbus A reference 1 as the
source for speed reference 1.