ABB ACS880 Series Firmware Manual page 346

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

346 Parameters
No.
Name/Value
Torque
Speed
Frequency
60.13
M/F act2 type
Auto
Transparent
General
Torque
Speed
Frequency
60.14
M/F follower
selection
Follower node 2
Follower node 3
Follower node 4
Follower nodes 2+3 Data is read from the followers with node addresses 2 and 3.
Follower nodes 2+4 Data is read from the followers with node addresses 2 and 4.
Follower nodes 3+4 Data is read from the followers with node addresses 3 and 4.
Follower nodes
2+3+4
None
60.15
Force master
FALSE
TRUE
Other [bit]
60.16
Force follower
FALSE
TRUE
Other [bit]
Description
01.10 Motor torque
is sent as actual value 1. The scaling is
defined by parameter
46.03 Torque
01.01 Motor speed used
is defined by parameter
01.06 Output frequency
is defined by parameter
Selects the type/source and scaling of actual value ACT2
transmitted to the master/follower link.
Type/source and scaling follow the type of reference 2
selected by parameter
60.11 M/F ref2
settings below for the sources and scalings.
Reserved.
Reserved.
01.10 Motor torque
is sent as actual value 2. The scaling is
defined by parameter
46.03 Torque
01.01 Motor speed used
is defined by parameter
01.06 Output frequency
is defined by parameter
(Effective in the master only.) Defines the followers from
which data is read. See also parameters 62.28...62.33.
Data is read from the follower with node address 2.
Data is read from the follower with node address 3.
Data is read from the follower with node address 4.
Data is read from the followers with node addresses 2, 3 and
4.
None.
When parameter
60.03 M/F mode
D2D
forcing, this parameter selects a source that forces the
drive to be the master on the master/follower link.
1 = Drive is master on the master/follower link
0.
1.
Source selection (see
Terms and abbreviations
When parameter
60.03 M/F mode
D2D
forcing, this parameter selects a source that forces the
drive to be a follower on the master/follower link.
1 = Drive is follower on the master/follower link
0.
1.
Source selection (see
Terms and abbreviations
scaling.
is sent as actual value 1. The scaling
46.01 Speed
scaling.
is sent as actual value 1. The scaling
46.02 Frequency
scaling.
type. See the individual
scaling.
is sent as actual value 2. The scaling
46.01 Speed
scaling.
is sent as actual value 2. The scaling
46.02 Frequency
scaling.
is set to
DDCS forcing
on page 112). -
is set to
DDCS forcing
on page 112). -
Def/FbEq16
3
4
5
Auto
0
1
2
3
4
5
None
2
4
8
6
10
12
14
0
or
FALSE
0
1
or
FALSE
0
1