ABB ACS880 Series Firmware Manual page 339

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

No.
Name/Value
58.15
Communication
loss mode
Any message
Cw / Ref1 / Ref2
58.16
Communication
loss time
0.0 ... 6000.0 s
58.17
Transmit delay
0...65535 ms
58.18
EFB control word
0000h...FFFFh
58.19
EFB status word
0000h...FFFFh
58.25
Control profile
ABB Drives
Transparent
58.26
EFB ref1 type
Auto
Transparent
General
Torque
Speed
Description
Defines which message types reset the timeout counter for
detecting an EFB communication loss.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
See also parameters
58.14 Communication loss action
58.16 Communication loss
Any message addressed to the drive resets the timeout.
A write of the control word or a reference from the fieldbus
resets the timeout.
Sets a timeout for EFB communication. If a communication
break lasts longer than the timeout, the action specified by
parameter
58.14 Communication loss action
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
See also parameter
58.15 Communication loss
EFB communication timeout.
Defines a minimum response delay in addition to any fixed
delay imposed by the protocol.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
Minimum response delay.
Displays the raw (unmodified) control word sent by the
Modbus controller to the drive. For debugging purposes.
This parameter is read-only.
Control word sent by Modbus controller to the drive.
Displays the raw (unmodified) status word sent by the drive to
the Modbus controller. For debugging purposes.
This parameter is read-only.
Status word sent by the drive to the Modbus controller.
Defines the control profile used by the protocol.
ABB Drives profile (with a 16-bit control word) with registers in
the classic format for backward compatibility.
Transparent profile (16-bit or 32-bit control word) with
registers in the classic format.
Selects the type and scaling of reference 1 received through
the embedded fieldbus interface.
The scaled reference is displayed by
Type and scaling are chosen automatically according to
which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. If the
reference is not connected to any chain, no scaling is applied
(as with setting Transparent).
No scaling is applied.
Generic reference with a scaling of 100 = 1 (ie. integer and
two decimals).
The scaling is defined by parameter
The scaling is defined by parameter
time.
is taken.
mode.
03.09 EFB reference
46.03 Torque
scaling.
46.01 Speed
scaling.
Parameters 339
Def/FbEq16
Cw / Ref1 /
Ref2
58.06
and
1
2
3.0 s
58.06
1 = 1
0 ms
58.06
1 = 1
-
1 = 1
-
1 = 1
ABB Drives
0
2
Auto
1.
0
1
2
3