No.
Name/Value
07.30
Adaptive program
status
Bit
Name
0
Initialized
1
Editing
2
Edit done
3
Running
4...13
Reserved
14
State changing
15
Faulted
0000h...FFFFh
10

10 Standard DI, RO

10.01
DI status
0000h...FFFFh
10.02
DI delayed status
0000h...FFFFh
10.03
DI force selection
Bit
Value
0
1 = Force DI1 to value of bit 0 of parameter
1
1 = Force DI2 to value of bit 1 of parameter
2
1 = Force DI3 to value of bit 2 of parameter
3
1 = Force DI4 to value of bit 3 of parameter
4
1 = Force DI5 to value of bit 4 of parameter
5
1 = Force DI6 to value of bit 5 of parameter
6...14
Reserved
15
1 = Force DIIL to value of bit 15 of parameter
0000h...FFFFh
Description
Shows the status of the adaptive program.
See section
Adaptive programming
Description
1 = Adaptive program initialized
1 = Adaptive program is being edited
1 = Editing of adaptive program finished
1 = Adaptive program running
1 = State change in progress in adaptive programming engine
1 = Error in adaptive program
Adaptive program status.
Configuration of digital inputs and relay outputs.
Displays the electrical status of digital inputs DIIL and
DI6...DI1. The activation/deactivation delays of the inputs (if
any are specified) are ignored. A filtering time can be defined
by parameter
10.51 DI filter
Bits 0...5 reflect the status of DI1...DI6; bit 15 reflects the
status of the DIIL input. Example: 1000000000010011b =
DIIL, DI5, DI2 and DI1 are on, DI3, DI4 and DI6 are off.
This parameter is read-only.
Status of digital inputs.
Displays the status of digital inputs DIIL and DI6...DI1. This
word is updated only after activation/deactivation delays (if
any are specified).
Bits 0...5 reflect the delayed status of DI1...DI6; bit 15
reflects the delayed status of the DIIL input.
This parameter is read-only.
Delayed status of digital inputs.
The electrical statuses of the digital inputs can be overridden
for eg. testing purposes. A bit in parameter
data
is provided for each digital input, and its value is applied
whenever the corresponding bit in this parameter is 1.
Override selection for digital inputs.
(page 27).
time.
10.04 DI force
10.04 DI force
data.
10.04 DI force
data.
10.04 DI force
data.
10.04 DI force
data.
10.04 DI force
data.
10.04 DI force
data.
10.04 DI force
data.
Parameters 141
Def/FbEq16
-
1 = 1
-
1 = 1
-
1 = 1
0000h
1 = 1