No.
Name/Value
95.15
Special HW
settings
Bit
Name
0
EX motor
1
ABB Sine filter
2
High speed mode
3...15
Reserved
0000b...0111b
Description
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
Information
1 = The driven motor is an Ex motor provided by ABB for potentially
explosive atmospheres. This sets the required minimum switching
frequency for ABB Ex motors. Note: For non-ABB Ex motors,
contact your local ABB representative.
1 = An ABB sine filter is connected to the output of the drive/inverter.
1 = Minimum switching frequency limit adaptation to output
frequency active. This setting improves control performance at high
output frequencies (typically above 120 Hz).
Hardware options configuration word.
Parameters 391
Def/FbEq16
-
1 = 1