ABB ACS880 Series Firmware Manual page 325

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

No.
Name/Value
Warning
50.03
FBA A comm loss t
out
0.3 ... 6553.5 s
50.04
FBA A ref1 type
Auto
Transparent
General
Torque
Speed
Frequency
50.05
FBA A ref2 type
50.07
FBA A actual 1 type
Auto
Transparent
General
Torque
Speed
Frequency
Description
Drive generates an
A7C1 FBA A communication
This occurs even though no control is expected from the
fieldbus.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Defines the time delay before the action defined by parameter
50.02 FBA A comm loss func
the communication link fails to update the message.
As a rule of thumb, this parameter should be set to at least 3
times the transmit interval of the master.
Time delay.
Selects the type and scaling of reference 1 received from
fieldbus adapter A.
Note: Fieldbus-specific communication profiles may use
different scalings. For more information, see the manual of
the fieldbus adapter.
Type and scaling are chosen automatically according to
which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. If the
reference is not connected to any chain, no scaling is applied
(as with setting Transparent).
No scaling is applied.
Generic reference with a scaling of 100 = 1 (ie. integer and
two decimals).
The scaling is defined by parameter
The scaling is defined by parameter
The scaling is defined by parameter
Selects the type and scaling of reference 2 received from
fieldbus adapter A.
See parameter
50.04 FBA A ref1
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through fieldbus adapter
A.
Note: Fieldbus-specific communication profiles may use
different scalings. For more information, see the manual of
the fieldbus adapter.
Type/source and scaling follow the type of reference 1
selected by parameter
50.04 FBA A ref1
individual settings below for the sources and scalings.
The value selected by parameter
transparent source
is sent as actual value 1. No scaling is
applied (the 16-bit scaling is 1 = 1 unit).
The value selected by parameter
transparent source
is sent as actual value 1 with a 16-bit
scaling of 100 = 1 unit (ie. integer and two decimals).
01.10 Motor torque
is sent as actual value 1. The scaling is
defined by parameter
46.03 Torque
01.01 Motor speed used
is defined by parameter
01.06 Output frequency
is defined by parameter
is taken. Time count starts when
46.03 Torque
46.01 Speed
46.02 Frequency
type.
type. See the
50.10 FBA A act1
50.10 FBA A act1
scaling.
is sent as actual value 1. The scaling
46.01 Speed
scaling.
is sent as actual value 1. The scaling
46.02 Frequency
scaling.
Parameters 325
Def/FbEq16
warning.
5
0.3 s
1 = 1 s
Auto
0
1
2
scaling.
3
scaling.
4
scaling. 5
Auto
Auto
0
1
2
3
4
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-01Acs880-37Acs880-04Acs880-07Acs880-17

Table of Contents