ABB ACS880 Series Firmware Manual page 350

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

350 Parameters
No.
Name/Value
60.27
M/F status supv
mode sel 1
Bit
Name
0
Follower 1
1
Follower 2
...
...
15
Follower 16
0000h...FFFFh
60.28
M/F status supv
mode sel 2
Bit
Name
0
Follower 17
1
Follower 18
...
...
15
Follower 32
0000h...FFFFh
60.31
M/F wake up delay
0.0 ... 180.0 s
Description
In the master, parameters
and
60.28 M/F status supv mode sel 2
follower status word monitoring. Each follower can
individually be set to be monitored continuously, or only when
it is in stopped state.
This parameter selects the mode of status word monitoring of
followers 1...16.
Description
0 = Status of follower 1 is monitored continuously.
1 = Status of follower 1 is monitored only when it is in stopped state.
0 = Status of follower 2 is monitored continuously.
1 = Status of follower 2 is monitored only when it is in stopped state.
...
0 = Status of follower 16 is monitored continuously.
1 = Status of follower 16 is monitored only when it is in stopped state.
M/F status supervision mode selection 1.
Selects the mode of status word monitoring of followers
17...32.
Description
0 = Status of follower 17 is monitored continuously.
1 = Status of follower 17 is monitored only when it is in stopped state.
0 = Status of follower 18 is monitored continuously.
1 = Status of follower 18 is monitored only when it is in stopped state.
...
0 = Status of follower 32 is monitored continuously.
1 = Status of follower 32 is monitored only when it is in stopped state.
M/F status supervision mode selection 2.
Defines a wake-up delay during which no master/follower
communication faults or warnings are generated. This is to
allow all drives on the master/follower link to power up.
The master cannot be started until the delay elapses or all
monitored followers are found to be ready.
Master/follower wake-up delay.
60.27 M/F status supv mode sel 1
specify the mode of
Def/FbEq16
-
1 = 1
-
1 = 1
60.0 s
10 = 1 s

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-01Acs880-37Acs880-04Acs880-07Acs880-17

Table of Contents