ABB ACS880 Series Firmware Manual page 273

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

No.
Name/Value
33.52
Value counter 1
function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 4 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 4 of 33.01) switches to 1,
and remains so until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.55) is given when the limit is reached
2...15
Reserved
0000b...0011b
33.53
Value counter 1
source
Not selected
Motor speed
Other
33.54
Value counter 1
divider
0.001 ...
2147483.000
33.55
Value counter 1
warn message
Value counter 1
exceeded
Maintain motor
bearing
33.60
Value counter 2
actual
-2147483008 ...
2147483008
Description
Configures value counter 1.
33.50
is reset. The warning (if enabled) also stays active until
Value counter 1 configuration word.
Selects the signal to be monitored by value counter 1.
None (counter disabled).
01.01 Motor speed used
Source selection (see
Terms and abbreviations
Defines a divisor for value counter 1. The value of the
monitored signal is divided by this value before integration.
Divisor for value counter 1.
Selects the optional warning message for value counter 1.
A88A Value counter
1. The message text can be edited on
the control panel by choosing Menu – Settings – Edit texts.
A880 Motor
bearing.
Displays the actual present value of value counter 2.
The value of the source selected by parameter
counter 2 source
is read at one-second intervals and added
to the counter. A divisor can be applied to the count (see
33.64 Value counter 2
divider).
When the counter exceeds the limit set by
counter 2 warn
limit, bit 5 of
The warning specified by
message
is also given if enabled by
function.
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
Actual present value of value counter 2.
(see page 115).
on page 112). -
33.63 Value
33.61 Value
33.01 Counter status
33.65 Value counter 2 warn
33.62 Value counter 2
Parameters 273
Def/FbEq16
0000b
33.50
1 = 1
Not selected
0
1
1.000
-
Value
counter 1
exceeded
4
10
-
is set to 1.
-