ABB ACS880 Series Firmware Manual page 497

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

Code
Fault
(hex)
5697
Charging feedback
5698
Unknown power unit
fault
6000
Internal SW error
6181
FPGA version
incompatible
6200
Checksum mismatch
Programmable fault:
Checksum action
6306
FBA A mapping file
6307
FBA B mapping file
6481
Task overload
6487
Stack overflow
64A1
Internal file load
64A2
Internal record load
64A3
Application loading
Cause
Incorrect parameter setting.
The charging switch and DC
switch were operated out of
sequence, or a start command
was issued before the unit was
ready.
Charging circuit fault.
Unidentified power unit logic
fault.
Internal error.
Firmware and FPGA file
version in the power unit are
incompatible.
The calculated parameter
checksum does not match any
96.54
enabled reference checksum.
Fieldbus adapter A mapping
file read error.
Fieldbus adapter B mapping
file read error.
Internal fault.
Internal fault.
File read error.
Internal record load error.
Application file incompatible or
corrupted.
8006 Not enough memory for the
application.
Fault tracing 497
What to do
Check the setting of
95.09 Fuse switch
control. The parameter should be
enabled only if an xSFC charging
controller is installed.
The normal power-up sequence is:
1. Close charging switch.
2. After charging finishes (charging OK
lamp lights), close DC switch.
3. Open charging switch.
Check the charging circuit.
With a frame R6i/R7i inverter module, the
auxiliary code "FA" indicates that the
charging contactor status feedback does
not match the control signal.
With parallel-connected frame R8i
modules, the auxiliary code (format
XX00), "XX" specifies the affected BCU
control unit channel.
Check power unit logic and firmware
compatibility.
Contact your local ABB representative.
Contact your local ABB representative,
quoting the auxiliary code.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
See
A686 Checksum mismatch
477).
Contact your local ABB representative.
Contact your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Contact your local ABB representative.
Check the auxiliary code. See actions for
each code below.
(page