392 Parameters
No.
Name/Value
95.20
HW options word 1
Bit
Name
0
Supply frequency
60 Hz
1
Emergency stop
Cat 0
2
Emergency stop
Cat 1
3
RO2 for -07
cabinet cooling fan
4
Externally powered
control unit
5
DC supply switch
6
DOL motor switch 1 = Motor fan control active. Affects 10.24, 35.100, 35.103, 35.104.
7
xSFC-01 fuse
switch controller
8
Service switch
9
Output contactor
10
Brake resistor, sine
filter, IP54 fan
11
INU-DSU
communication
12
Reserved
13
du/dt filter
activation
14
DOL fan activation 1 = The inverter unit consists of frame R8i modules with direct-on-
15
INU-ISU
communication
0000h...FFFFh
Description
Specifies hardware-related options that require differentiated
parameter defaults. Activating a bit in this parameter makes
the necessary changes in other parameters – for example,
activating an emergency stop option reserves a digital input.
In many cases, the differentiated parameters will also be
write-protected.
This parameter, as well as the changes in other parameters
implemented by it, are not affected by a parameter restore.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Information
0 = 50 Hz; 1 = 60 Hz. Affects parameters 11.45, 11.59, 12.20, 13.18,
30.11, 30.12, 30.13, 30.14, 31.26, 31.27, 40.15, 40.37, 41.15, 41.37,
46.01, 46.02.
1 = Emergency stop, Category 0, without FSO module. Affects
21.04, 21.05, 23.11.
1 = Emergency stop, Category 1, without FSO module. Affects
10.24, 21.04, 21.05, 23.11.
1 = Control of cabinet cooling fan (used only with specific
ACS880-07 hardware). Affects 10.27, 10.28, 10.29.
1 = Control unit powered externally. Affects 95.04.
1 = DC switch monitoring active. Affects 20.12, 31.03, 95.08.
1 = xSFC charging controller used. Affects 95.09.
1 = Service switch connected. Affects 31.01, 31.02.
1 = Output contactor present. Affects 10.24, 20.12.
1 = Status (eg. thermal) switches connected to DIIL input. Affects
20.11, 20.12.
1 = Diode supply unit control by inverter unit active. Affects 60.71,
61.151, 62.151, 94.01.
1 = Active: A du/dt filter is connected to the drive/inverter output.
Note: This bit is to be left at 0 if the drive/inverter module is
equipped with internal du/dt filtering (for example, frame R8i inverter
modules with option +E205).
line cooling fans (option +C188). Disables fan feedback monitoring
and changes fan control to ON/OFF type.
1 = IGBT supply unit control by inverter unit active. Affects 60.71,
61.151, 61.152, 61.153, 62.151, 94.01.
Hardware options configuration word 1.
Def/FbEq16
-
1 = 1