272 Parameters
No.
Name/Value
33.45
Edge counter 2
warn message
Edge counter 2
exceeded
Counted main
contactor
Counted output
relay
Counted motor
starts
Counted power ups
Counted DC
charges
33.50
Value counter 1
actual
-2147483008 ...
2147483008
33.51
Value counter 1
warn limit
-2147483008 ...
2147483008
Description
Selects the optional warning message for signal edge counter
2.
A889 Edge counter
2. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
A884 Main
contactor.
A881 Output
relay.
A882 Motor
starts.
A883 Power
ups.
A885 DC
charge.
Displays the actual present value of value counter 1.
The value of the source selected by parameter
counter 1 source
is read at one-second intervals and added
to the counter. A divisor can be applied to the count (see
33.54 Value counter 1
divider).
When the counter exceeds the limit set by
counter 1 warn
limit, bit 4 of
The warning specified by
message
is also given if enabled by
function.
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
Actual present value of value counter 1.
Sets the limit for value counter 1.
With a positive limit, bit 4 of
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 4 of
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
Limit for value counter 1.
33.53 Value
33.51 Value
33.01 Counter status
33.55 Value counter 1 warn
33.52 Value counter 1
33.01 Counter status
33.01 Counter status
Def/FbEq16
Edge counter
2 exceeded
3
11
12
13
14
15
-
is set to 1.
-
0
is set to 1
is set to 1
-