Technical Data; Chapter Overview; Environmental Conditions - ABB DCS880 series Hardware Manual

20 ... 5200 a
Hide thumbs Also See for DCS880 series:
Table of Contents

Advertisement

Technical data

Chapter overview

The technical data contain the technical specifications of the converter, e.g. the
ratings, sizes and technical requirements, provisions for fulfilling the requirements for
CE and other markings and warranty policy.

Environmental Conditions

System connections
Voltage, 3-phase:
Voltage deviation:
Rated frequency:
Static frequency deviation:
Dynamic: frequency range:
df/dt:
* = 0.5 ... 30 cycles
Please note: Special consideration must be taken for voltage
deviation in regenerative mode.
Degree of protection
Converter module and options
(line chokes, fuse holder, field
exciter, etc.):
Enclosed converters:
Paint finish
Converter module:
Enclosed converter:
Sound pressure level and vibration
Size Sound pressure level L
as module
enclosed conv.
H1
55 dBA
H2
55 dBA
H3
60 dBA
H4
66 ... 70 dBA,
depending on fan
H5
75 dBA
H6
70 dBA
H7
69 dBA
H8
82 dBA
100 ... 1000 V acc. to IEC 60038
±10 % continuous; ±15% short-time *
50 Hz or 60 Hz
50 Hz ± 2 %; 60 Hz ± 2 %
50 Hz ± 5 Hz; 60 Hz ± 5 Hz
17 % / s
IP 00
IP 20/21/31/41
RAL 7012
Light grey RAL 7035
(1 m distance)
Vibration
P
as module
68 dBA
0.5 g, 5 ... 55 Hz
72 dBA
78 dBA
77 dBA
77 dBA
1 mm, 2 ... 9 Hz
78 dBA
67 dBA
0.3 mm, 2 ... 9 Hz
80 dBA
3ADW000462R0101 DCS880 Hardware Manual e a
Environmental limit values
Permissible cooling air temp.
- at converter module air inlet:
with rated DC current:
with different DC current:
- Options:
Relative humidity (at 5...+40°C): 5 ... 95 %, no condensation
Relative humidity (at 0...+5°C):
Change of the ambient temp.:
Storage temperature:
Transport temperature:
Pollution degree (IEC 60664-1,
IEC 60439-1):
Site elevation
< 1000 m above M.S.L.:
> 1000 m above M.S.L.:
North American Standards
In North America the system components fulfil the requirements of
the table below.
Rated supply
Converter module
voltage
to 600 V
UL 61800-5-1
Power Conversion Equipment
CSA C 22.2 No. 274-13
Industrial Control Equipment,
Industrial Products
Available for converter mod-
ules including field exciter
units. Types with UL mark:
• see UL Listing www.ul.com /
certificate no. E196914
• or on request
0 ... +55°C
0 ... +40°C
+30 ... +55°C
0 ... +40°C
5 ... 50 %, no condensation
< 0.5°C / minute
-40 ... +55°C
-40 ... +70°C
2
100 %, without current reduction
with current reduction,
see figures next page
Standards
Enclosed converter
UL/CSA types: on
request
Technical data
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcs880-s series