264 Parameters
No.
Name/Value
32.05
Supervision 1
function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.06
Supervision 1
action
No action
Warning
Fault
32.07
Supervision 1
signal
Zero
Speed
Frequency
Current
Torque
DC voltage
Output power
AI1
AI2
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torque ref used
Freq ref used
Process PID output
Process PID
feedback
Other
Description
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter 32.07) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.06.
Signal supervision 1 not in use.
Action is taken whenever the signal falls below its lower limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Selects the action the drive takes when the value monitored
by signal supervision 1 exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No action taken.
A warning
(A8B0 Signal
The drive trips on
80B0 Signal
Selects the signal to be monitored by signal supervision
function 1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 115).
01.10 Motor torque
(page 115).
01.11 DC voltage
(page 115).
01.14 Output power
(page 116).
12.11 AI1 actual value
(page 153).
12.21 AI2 actual value
(page 155).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
26.02 Torque reference used
28.02 Frequency ref ramp output
40.01 Process PID output actual
40.02 Process PID feedback actual
Source selection (see
Terms and abbreviations
(32.09
and
32.10
respectively).
supervision) is generated.
supervision.
(page 115).
(page 115).
(page 213).
(page 213).
(page 219).
(page 233).
(page 239).
(page 293).
(page 293).
on page 112). -
Def/FbEq16
Disabled
0
1
2
3
4
5
6
No action
0
1
2
Zero
0
1
3
4
6
7
8
9
10
18
19
20
21
22
24
25