336 Parameters
No.
Name/Value
Ref2 16bit
CW 32bit
Ref1 32bit
Ref2 32bit
CW2 16bit
Other
...
...
56.12
FBA B data out12
58

58 Embedded fieldbus

58.01
Protocol enable
None
Modbus RTU
58.02
Protocol ID
58.03
Node address
0...255
58.04
Baud rate
9.6 kbps
19.2 kbps
38.4 kbps
57.6 kbps
76.8 kbps
115.2 kbps
58.05
Parity
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
Description
Reference REF2 (16 bits)
Control Word (32 bits)
Reference REF1 (32 bits)
Reference REF2 (32 bits)
Control Word 2 (16 bits)
Source selection (see
Terms and abbreviations
...
See parameter
56.01 FBA B data out1.
Configuration of the embedded fieldbus (EFB) interface.
See also chapter
Fieldbus control through the embedded
fieldbus interface (EFB)
Enables/disables the embedded fieldbus interface and
selects the protocol to use.
Note: When the embedded fieldbus interface is enabled, the
drive-to-drive link functionality is automatically disabled.
None (communication disabled).
Embedded fieldbus interface is enabled and uses the Modbus
RTU protocol.
Displays the protocol ID and revision.
This parameter is read-only.
Protocol ID and revision.
Defines the node address of the drive on the fieldbus link.
Values 1...247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
Node address (values 1...247 are allowable).
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
9.6 kbit/s.
19.2 kbit/s.
38.4 kbit/s.
57.6 kbit/s.
76.8 kbit/s.
115.2 kbit/s.
Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
Eight data bits, no parity bit, one stop bit.
Eight data bits, no parity bit, two stop bits.
Eight data bits, even parity bit, one stop bit.
Eight data bits, odd parity bit, one stop bit.
on page 112). -
(page 509).
Def/FbEq16
3
11
12
13
21
...
None
None
0
1
-
1 = 1
1
58.06
1 = 1
19.2 kbps
58.06
2
3
4
5
6
7
8 EVEN 1
58.06
0
1
2
3