ABB ACS880 Series Firmware Manual page 132

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

132 Parameters
No.
Name/Value
06.20
Constant speed
status word
Bit
Name
0
Constant speed 1
1
Constant speed 2
2
Constant speed 3
3
Constant speed 4
4
Constant speed 5
5
Constant speed 6
6
Constant speed 7
7...15
Reserved
0000h...FFFFh
06.21
Drive status word 3
Bit
Name
0
DC hold active
1
Post-magnetizing
active
2
Motor pre-heating
active
3
PM smooth start active Reserved.
4...15
Reserved
0000h...FFFFh
06.25
Drive inhibit status
word 2
Bit
Name
0
Follower drive
1
Application
2
Aux. power failure
3
Encoder feedback
4
Ref source
parametrization
5...15
Reserved
0000h...FFFFh
Description
Constant speed/frequency status word. Indicates which
constant speed or frequency is active (if any). See also
parameter
06.19 Speed control status
Constant speeds/frequencies
This parameter is read-only.
Description
1 = Constant speed or frequency 1 selected
1 = Constant speed or frequency 2 selected
1 = Constant speed or frequency 3 selected
1 = Constant speed or frequency 4 selected
1 = Constant speed or frequency 5 selected
1 = Constant speed or frequency 6 selected
1 = Constant speed or frequency 7 selected
Constant speed/frequency status word.
Drive status word 3.
This parameter is read-only.
Description
1 = DC hold is active (see par. 21.08)
1 = Post-magnetizing is active (see par. 21.08)
1 = Motor pre-heating is active (see par. 21.14)
Drive status word 3.
Drive inhibit status word 2. This word specifies the source of
the inhibiting signal that is preventing the drive from starting.
See also parameter
06.18 Start inhibit status
Drive status word
1, bit 1.
This parameter is read-only.
Description
1 = A follower is preventing the master from starting.
1 = The application program is preventing the drive from starting.
1 = A control unit auxiliary power failure is preventing the drive
from starting.
1 = The encoder feedback configuration is preventing the drive
from starting.
1 = A reference source parametrization conflict is preventing the
drive from starting. See warning
parametrization
Start inhibit status word.
word, bit 7, and section
(page 45).
word, and
A6DA Reference source
(page 479).
Def/FbEq16
-
1 = 1
-
1 = 1
-
06.16
1 = 1