ABB ACS880 Series Firmware Manual page 394

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

394 Parameters
No.
Name/Value
Français
Dansk
Suomi
Svenska
Russki
Polski
Czech
Chinese (Simplified,
PRC)
Türkçe
96.02
Pass code
0...99999999
96.03
Access levels
active
Bit
Name
0
End user
1
Service
2
Advanced programmer
3...10
Reserved
11
OEM access level 1
12
OEM access level 2
13
OEM access level 3
14
Parameter lock
15
Reserved
0000h...FFFFh
96.04
Macro select
Done
Description
French.
Danish.
Finnish.
Swedish.
Russian.
Polish.
Czech.
Simplified Chinese.
Turkish.
Pass codes can be entered into this parameter to activate
further access levels (see parameter
active) or to configure the user lock.
Entering "358" toggles the parameter lock, which prevents the
changing of all other parameters through the control panel or
the Drive composer PC tool.
Entering the user pass code (by default, "10000000") enables
parameters 96.100...96.102, which can be used to define a
new user pass code and to select the actions that are to be
prevented.
Entering an invalid pass code will close the user lock if open,
ie. hide parameters 96.100...96.102. After entering the code,
check that the parameters are in fact hidden.
Note: We recommend that you change the default user pass
code.
See also section
User lock
Pass code.
Shows which access levels have been activated by pass
codes entered into parameter
This parameter is read-only.
Active access levels.
Selects the application macro. See chapter
macros
(page 95) for more information.
After a selection is made, the parameter reverts automatically
to Done.
Macro selection complete; normal operation.
96.03 Access levels
(page 91).
96.02 Pass
code.
Application
Def/FbEq16
1036
1030
1035
1053
1049
1045
1029
2052
1055
0
-
0001h
-
Done
0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-01Acs880-37Acs880-04Acs880-07Acs880-17