No.
Name/Value
Refresh
49.07
Panel comm
supervision force
Bit
Name
0
Ext 1
1
Ext 2
2
Local
3...15
Reserved
0000b...0111b
49.08
Secondary comm.
loss action
No action
Warning
49.14
Panel speed
reference unit
rpm
%
49.15
Minimum ext speed
ref panel
-30000.00 ...
30000.00 rpm
49.16
Maximum ext
speed ref panel
-30000.00 ...
30000.00 rpm
Description
Refresh parameters 49.01...49.05. The value reverts
automatically to Done.
Activates control panel communication monitoring separately
for each control location (see section
external control
on page 20).
The parameter is primarily intended for monitoring the
communication with the panel when it is connected to the
application program and not selected as a control source by
drive parameters.
Value
1 = Communication monitoring active when Ext 1 is being used.
1 = Communication monitoring active when Ext 2 is being used.
1 = Communication monitoring active when local control is being
used.
Panel communication monitoring selection.
Selects how the drive reacts to a control panel (or PC tool)
communication break when the panel is parametrized as an
alternative control or reference source but is not currently the
active source.
No action taken.
Drive generates an
A7EE Control panel loss
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Defines the unit for speed reference when given from the
control panel.
rpm.
Percent of absolute value of
Minimum
speed, whichever is greater.
Defines a minimum limit for control panel speed reference in
external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
20).
Minimum speed reference.
Defines a maximum limit for control panel speed reference in
external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
20).
Maximum speed reference.
Local control vs.
warning.
30.12 Maximum speed
or
30 Limits
(page
30 Limits
(page
Parameters 323
Def/FbEq16
1
0000b
1 = 1
No action
0
5
rpm
0
30.11
1
-30000.00
rpm
are in
See par.
46.01
30000.00
rpm
are in
See par.
46.01