402 Parameters
No.
Name/Value
96.101 Confirm user pass
code
10000000...
99999999
96.102 User lock
functionality
Bit
Name
0
Disable ABB access
levels
1
Freeze parameter
lock state
2
Disable file
download
3...15
Reserved
000b...111b
96

97 Motor control

97.03
Slip gain
0 ... 200%
Description
(Visible when user lock is open)
Confirms the new user pass code entered in
user pass
code.
Confirmation of new user pass code.
(Visible when user lock is open)
Selects the actions or functionalities to be prevented by the
user lock. Note that the changes made take effect only when
the user lock is closed. See parameter
Information
1 = ABB access levels (service, advanced programmer, etc.; see
96.03) disabled
1 = Changing the parameter lock state prevented, ie. pass code
358 has no effect
1 = Loading of files to drive prevented. This applies to
• firmware upgrades
• safety functions module (FSO-xx) configuration
• parameter restore
• loading of adaptive or application programs
• changing home view of control panel
• editing drive texts
• editing the favorite parameters list on control panel
• configuration settings made through control panel such as
time/date formats and enabling/disabling clock display.
Selection of actions to be prevented by user lock.
Motor model settings.
Defines the slip gain which is used to improve the estimated
motor slip. 100% means full slip gain; 0% means no slip gain.
The default value is 100%. Other values can be used if a
static speed error is detected despite having the setting at full
slip gain.
Example (with nominal load and nominal slip of 40 rpm): A
1000 rpm constant speed reference is given to the drive.
Despite having full slip gain (= 100%), a manual tachometer
measurement from the motor axis gives a speed value of 998
rpm. The static speed error is 1000 rpm - 998 rpm = 2 rpm. To
compensate the error, the slip gain should be increased to
105% (2 rpm / 40 rpm = 5%).
Slip gain.
96.100 Change
96.02 Pass
code.
Def/FbEq16
-
000b
-
100%
1 = 1%