488 Fault tracing
Code
Warning
(hex)
AF85
Line side unit warning
AF8C
Process PID sleep
mode
AF90
Speed controller
autotuning
AFAA
Autoreset
AFE1
Emergency stop (off2)
AFE2
Emergency stop (off1
or off3)
Cause
The supply unit has generated
a warning.
The drive is entering sleep
mode.
The speed controller autotune
routine did not complete
successfully.
0000 The drive was stopped before
the autotune routine finished.
0001 The drive was started but was
not ready to follow the
autotune command.
0002 Required torque reference
could not be reached before
the drive reached maximum
speed.
0003 Motor could not
accelerate/decelerate to
maximum/minimum speed.
0005 Motor could not decelerate
with full autotune torque.
A fault is about to be autoreset. Informative warning. See the settings in
Drive has received an
emergency stop (mode
selection off2) command.
(Follower drive in a
master/follower configuration)
Drive has received a stop
command from the master.
Drive has received an
emergency stop (mode
selection Off1 or Off3)
command.
What to do
If using a control panel or the Drive
composer tool, connect to the supply unit
to read the warning code. Refer to the
firmware manual of the supply unit for
instructions related to the code.
Informative warning. See section
function for process PID control
68), and parameters 40.41...40.48.
Check the auxiliary code (format XXXX
YYYY). "YYYY" indicates the problem
(see actions for each code below).
Repeat autotune until successful.
Make sure the prerequisites of the
autotune run are fulfilled. See section
Before activating the autotune routine
(page 46).
Decrease torque step (parameter 25.38)
or increase speed step (25.39).
Increase torque step (parameter 25.38)
or decrease speed step (25.39).
Decrease torque step (parameter 25.38)
or speed step (25.39).
parameter group
31 Fault
Check that it is safe to continue
operation. Reset the source of the
emergency stop signal (such as an
emergency stop push button). Restart
drive.
If the emergency stop was unintentional,
check the source of the stop signal (for
example,
21.05 Emergency stop
or control word received from an external
control system).
Informative warning. After stopping on a
ramp stop (Off1 or Off3) command, the
master sends a short, 10-millisecond
coast stop (Off2) command to the
follower(s). The Off2 stop is stored in the
event log of the follower.
Check that it is safe to continue
operation. Reset the source of the
emergency stop signal (such as an
emergency stop push button). Restart
drive.
If the emergency stop was unintentional,
check the source of the stop signal (for
example,
21.05 Emergency stop
or control word received from an external
control system).
Sleep
(page
functions.
source,
source,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-01Acs880-37Acs880-04Acs880-07Acs880-17

Table of Contents