134 Parameters
No.
Name/Value
06.36
LSU Status Word
Bit
Name
0
Ready on
1
Ready run
2
Ready ref
3
Tripped
4...6
Reserved
7
Warning
8
Modulating
9
Remote
10
Net ok
11...12 Reserved
13
Charging or
ready run
14
Charging
15
Reserved
0000h...FFFFh
06.39
Internal state
machine LSU CW
Bit
Name
0
ON/OFF
1
OFF 2
2
OFF 3
3
START
4...6
Reserved
7
RESET
8...11
Reserved
12
USER BIT 0 See parameter
13
USER BIT 1 See parameter
14
USER BIT 2 See parameter
15
USER BIT 3 See parameter
0000h...FFFFh
Description
(Only visible with a
BCU
Shows the status of the supply unit.
See also section
Control of a supply unit (LSU)
and parameter group
60 DDCS
This parameter is read-only.
Description
1 = Ready to switch on
1 = Ready to operate, DC link charged
1 = Operation enabled
1 = A fault is active
1 = A warning is active
1 = The supply unit is modulating
1 = Remote control (EXT1 or EXT2)
0 = Local control
1 = Supply network voltage OK
1 = Bit 1 or bit 14 active
1 = Charging contactor closed
0 = Charging contactor open
Supply unit status word.
(Only visible with a
BCU
Shows the control word sent to the supply unit from the INU-
LSU (inverter unit/supply unit) state machine.
This parameter is read-only.
Description
1 = Start charging
0 = Open main contactor (switch power off)
0 = Emergency stop (Off2)
0 = Emergency stop (Off3)
1 = Start modulating
0 = Stop modulating
0 - > 1 = Reset an active fault. A fresh start command is required after reset.
06.40 LSU CW user bit 0
06.41 LSU CW user bit 1
06.42 LSU CW user bit 2
06.43 LSU CW user bit 3
Supply unit control word.
control unit)
(page 42),
communication.
control unit)
selection.
selection.
selection.
selection.
Def/FbEq16
-
1 = 1
-
1 = 1