ABB ACS880 Series Firmware Manual page 507

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

Code
Fault
(hex)
000E...0010 Internal error.
FF7E
Follower
FF81
FB A force trip
FF82
FB B force trip
FF8E
EFB force trip
Cause
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
000B (Asynchronous motors only)
Speed dropped to zero during
ID run.
000C (Permanent magnet motors
only) First acceleration did not
finish within reasonable time.
000D (Permanent magnet motors
only) Second acceleration did
not finish within reasonable
time.
A follower drive has tripped.
A fault trip command has been
received through fieldbus
adapter A.
A fault trip command has been
received through fieldbus
adapter B.
A fault trip command has been
received through the
embedded fieldbus interface.
Fault tracing 507
What to do
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check the auxiliary code. Add 2 to the
code to find out the node address of the
faulted drive.
Correct the fault in the follower drive.
Check the fault information provided by
the PLC.
Check the fault information provided by
the PLC.
Check the fault information provided by
the Modbus controller.