No.
Name/Value
58.31
EFB act1
transparent source
Not selected
Other
58.32
EFB act2
transparent source
Not selected
Other
58.33
Addressing mode
Mode 0
Mode 1
Mode 2
58.34
Word order
HI-LO
LO-HI
Description
Selects the source of actual value 1 when
type
is set to
Transparent
None.
Source selection (see
Terms and abbreviations
Selects the source of actual value 1 when
type
is set to
Transparent
None.
Source selection (see
Terms and abbreviations
Defines the mapping between parameters and holding
registers in the 400101...465535 Modbus register range.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
16-bit values (groups 1...99, indexes 1...99):
Register address = 400000 + 100 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 2200 + 80 = 402280.
32-bit values (groups 1...99, indexes 1...99):
Register address = 420000 + 200 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 420000 + 4400 + 160 = 424560.
16-bit values (groups 1...255, indexes 1...255):
Register address = 400000 + 256 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 5632 + 80 = 405712.
32-bit values (groups 1...127, indexes 1...255):
Register address = 400000 + 512 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 11264 + 160 = 411424.
Selects in which order 16-bit registers of 32-bit parameters
are transferred.
For each register, the first byte contains the high order byte
and the second byte contains the low order byte.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
The first register contains the high order word, the second
contains the low order word.
The first register contains the low order word, the second
contains the high order word.
58.28 EFB act1
or General.
on page 112). -
58.29 EFB act2
or General.
on page 112). -
Parameters 341
Def/FbEq16
Not selected
0
Not selected
0
Mode 0
58.06
0
1
2
LO-HI
58.06