ABB ACS880 Series Firmware Manual page 257

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

No.
Name/Value
31.13
User selectable
fault
0000h...FFFFh
31.14
Number of trials
0...5
31.15
Total trials time
1.0 ... 600.0 s
31.16
Delay time
0.0 ... 120.0 s
31.19
Motor phase loss
No action
Fault
31.20
Earth fault
No action
Warning
Fault
31.21
Supply phase loss
No action
Fault
Description
Defines the fault that can be automatically reset using
parameter
31.12 Autoreset
The faults are listed in chapter
Fault code.
Defines the maximum number of automatic resets that the
drive is allowed to attempt within the time specified by
Total trials
time.
If the fault persists, subsequent reset attempts will be made at
intervals defined by
31.16 Delay
The faults to be automatically reset are defined by
Autoreset
selection.
Number of automatic resets.
Defines a time window for automatic fault resets. The
maximum number of attempts made during any period of this
length is defined by
31.14 Number of
Note: If the fault condition remains and cannot be reset, each
reset attempt will generate an event and start a new time
window. In practice, if the specified number of resets (31.14)
at specified intervals (31.16) take longer than the value of
31.15, the drive will continue to attempt resetting the fault until
the cause is eventually removed.
Time for automatic resets.
Defines the time that the drive will wait after a fault (or a
previous reset attempt) before attempting an automatic reset.
See parameter
31.12 Autoreset
Autoreset delay.
Selects how the drive reacts when a motor phase loss is
detected.
No action taken.
The drive trips on fault
3381 Output phase
Selects how the drive reacts when an earth fault or current
unbalance is detected in the motor or the motor cable.
No action taken.
The drive generates an
The drive trips on fault
2330 Earth
Selects how the drive reacts when a supply phase loss is
detected.
No action taken.
The drive trips on fault
3130 Input phase
selection, bit 10.
Fault tracing
(page 490).
time.
trials.
selection.
loss.
A2B3 Earth leakage
warning.
leakage.
loss.
Parameters 257
Def/FbEq16
0000h
10 = 1
0
31.15
31.12
-
30.0 s
10 = 1 s
0.0 s
10 = 1 s
Fault
0
1
Fault
0
1
2
Fault
0
1