No.
Name/Value
96.61
User data logger
status word
Bit
Name
0
Running
1
Triggered
2
Data
available
3
Configured
4...15
Reserved
0000b...1111b
96.63
User data logger
trigger
Off
On
Other [bit]
96.64
User data logger
start
Off
On
Other [bit]
96.65
Factory data logger
time level
500us
2ms
10ms
96.70
Disable adaptive
program
No
Yes
96.100 Change user pass
code
10000000...
99999999
Description
Provides status information on the user data logger (see page
471).
Description
1 = The user data logger is running. The bit is cleared after the post-trigger
time has passed.
1 = The user data logger has been triggered. The bit is cleared when the
logger is restarted.
1 = The user data logger contains data that can be read. Note that the bit is
not cleared because the data is saved to the memory unit.
1 = The user data logger has been configured. Note that the bit is not
cleared because the configuration data is saved to the memory unit.
User data logger status word.
Triggers, or selects a source that triggers, the user data
logger.
0.
1.
Source selection (see
Terms and abbreviations
Starts, or selects a source that starts, the user data logger.
0.
1.
Source selection (see
Terms and abbreviations
Selects the sampling interval for the factory data logger (see
page 470).
500 microseconds.
2 milliseconds.
10 milliseconds.
Enables/disables the adaptive program (if present).
See also section
Adaptive programming
Adaptive program enabled.
Adaptive program disabled.
(Visible when user lock is open)
To change the current user pass code, enter a new code into
this parameter as well as
warning will be active until the new pass code is confirmed.
To cancel changing the pass code, close the user lock without
confirming. To close the lock, enter an invalid pass code in
parameter
96.02 Pass
code, activate parameter
Control board
boot, or cycle the power.
See also section
User lock
New user pass code.
on page 112). -
on page 112). -
(page 27).
96.101 Confirm user pass
96.08
(page 91).
Parameters 401
Def/FbEq16
0000b
1 = 1
Off
0
1
Off
0
1
500us
500
2000
10000
No
0
1
10000000
code. A
-