Automatic restart
It is possible to restart the drive automatically after a short (max. 5 seconds) power
supply failure by using the Automatic restart function provided that the drive is
allowed to run for 5 seconds without the cooling fans operating.
When enabled, the function takes the following actions upon a supply failure to
enable a successful restart:
• The undervoltage fault is suppressed (but a warning is generated)
• Modulation and cooling is stopped to conserve any remaining energy
• DC circuit pre-charging is enabled.
If the DC voltage is restored before the expiration of the period defined by parameter
21.18 Auto restart time
However, if the DC voltage remains too low at that point, the drive trips on a fault,
3280 Standby
timeout.
WARNING! Before you activate the function, make sure that no dangerous
situations can occur. The function restarts the drive automatically and
continues operation after a supply break.

Voltage control and trip limits

The control and trip limits of the intermediate DC voltage regulator are relative to the
supply voltage as well as drive/inverter type. The DC voltage is approximately 1.35
times the line-to-line supply voltage, and is displayed by parameter
The following table shows the values of selected DC voltage levels in volts. All
voltages are relative to the supply voltage range selected in parameter
voltage.
and the start signal is still on, normal operation will continue.
Program features 77
01.11 DC
voltage.