ABB ACS880 Series Firmware Manual page 337

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

No.
Name/Value
58.06
Communication
control
Enabled
Refresh settings
Silent mode
58.07
Communication
diagnostics
Bit
Name
0
Init failed
1
Addr config err
2
Silent mode
3
Autobauding
4
Wiring error
5
Parity error
6
Baud rate error
7
No bus activity
8
No packets
9
Noise or addressing
error
10
Comm loss
11
CW/Ref loss
12
Not active
13
Protocol 1
14
Protocol 2
15
Internal error
0000h...FFFFh
58.08
Received packets
0...4294967295
58.09
Transmitted packets
0...4294967295
Description
Validates any changes in the EFB settings, or activates silent
mode.
Normal operation.
Validates any changed EFB configuration settings. Reverts
automatically to Enabled.
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
settings
selection of this parameter.
Displays the status of the EFB communication.
This parameter is read-only.
Description
1 = EFB initialization failed
1 = Node address not allowed by protocol
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
Reserved
1 = Errors detected (A/B wires possibly swapped)
1 = Error detected: check parameters
1 = Error detected: check parameters
1 = 0 bytes received during last 5 seconds
1 = 0 packets (addressed to any device) detected during last 5
seconds
1 = Errors detected (interference, or another device with the
same address on line)
1 = 0 packets addressed to the drive received within timeout
(58.16)
1 = No control word or references received within timeout
(58.16)
Reserved
Reserved
Reserved
Reserved
EFB communication status.
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
Number of received packets addressed to the drive.
Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
Number of transmitted packets.
Parameters 337
Def/FbEq16
Enabled
0
1
2
Refresh
-
58.04
and
58.05
58.05
and
58.04
1 = 1
-
1 = 1
-
1 = 1