288 Parameters
No.
Name/Value
36.13
PVL current at peak
-32768.00 ...
32767.00 A
36.14
PVL DC voltage at
peak
0.00 ... 2000.00 V
36.15
PVL speed at peak
-32768.00 ...
32767.00 rpm
36.16
PVL reset date
-
36.17
PVL reset time
-
36.20
AL1 0 to 10%
0.00 ... 100.00%
36.21
AL1 10 to 20%
0.00 ... 100.00%
36.22
AL1 20 to 30%
0.00 ... 100.00%
36.23
AL1 30 to 40%
0.00 ... 100.00%
36.24
AL1 40 to 50%
0.00 ... 100.00%
36.25
AL1 50 to 60%
0.00 ... 100.00%
36.26
AL1 60 to 70%
0.00 ... 100.00%
36.27
AL1 70 to 80%
0.00 ... 100.00%
36.28
AL1 80 to 90%
0.00 ... 100.00%
36.29
AL1 over 90%
0.00 ... 100.00%
Description
Displays the motor current at the moment the peak value was
recorded.
Motor current at peak.
Displays the voltage in the intermediate DC circuit of the drive
at the moment the peak value was recorded.
DC voltage at peak.
Displays the motor speed at the moment the peak value was
recorded.
Motor speed at peak.
Displays the date on which the peak value logger was last
reset.
Last reset date of the peak value logger.
Displays the time at which the peak value logger was last
reset.
Last reset time of the peak value logger.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 0 and 10%.
Amplitude logger 1 samples between 0 and 10%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 10 and 20%.
Amplitude logger 1 samples between 10 and 20%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 20 and 30%.
Amplitude logger 1 samples between 20 and 30%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 30 and 40%.
Amplitude logger 1 samples between 30 and 40%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 40 and 50%.
Amplitude logger 1 samples between 40 and 50%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 50 and 60%.
Amplitude logger 1 samples between 50 and 60%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 60 and 70%.
Amplitude logger 1 samples between 60 and 70%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 70 and 80%.
Amplitude logger 1 samples between 70 and 80%.
Displays the percentage of samples recorded by amplitude
logger 1 that fall between 80 and 90%.
Amplitude logger 1 samples between 80 and 90%.
Displays the percentage of samples recorded by amplitude
logger 1 that exceed 90%.
Amplitude logger 1 samples over 90%.
Def/FbEq16
0.00 A
1 = 1 A
0.00 V
10 = 1 V
0.00 rpm
See par.
46.01
-
-
-
-
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%