No.
Name/Value
97.13
IR compensation
0.00 ... 50.00%
97.15
Motor model
temperature
adaptation
Disabled
Estimated
temperature
Measured
temperature 1
Measured
temperature 2
97.32
Motor torque
unfiltered
-1600.0 ... 1600.0% Unfiltered motor torque.
97.33
Speed estimate
filter time
0.00 ... 100.00 ms
Description
Defines the relative output voltage boost at zero speed (IR
compensation). The function is useful in applications with a
high break-away torque where direct torque control (DTC
mode) cannot be applied.
U / U
N
(%)
Relative output voltage with IR
compensation
100%
97.13
Field weakening point
50% of nominal frequency
See also section
IR compensation for scalar motor control
page 60.
Voltage boost at zero speed in percent of nominal motor
voltage.
Selects whether the temperature-dependent parameters
(such as stator or rotor resistance) of the motor model adapt
to actual (measured or estimated) temperature or not.
See parameter group
35 Motor thermal protection
selection of temperature measurement sources.
Temperature adaptation of motor model disabled.
Estimated temperature
(35.01 Motor estimated
used for adaptation of motor model.
Measured temperature 1
used for adaptation of motor model.
Measured temperature 2
used for adaptation of motor model.
Unfiltered motor torque in percent of the nominal motor
torque.
Defines a filtering time for estimated speed. See the diagram
on page 549.
Filtering time for estimated speed.
Relative output voltage. No
IR compensation.
temperature)
(35.02 Measured temperature
(35.03 Measured temperature
Parameters 405
Def/FbEq16
0.00%
f (Hz)
on
1 = 1%
Disabled
for
0
1
1)
2
2)
3
-
See par.
46.03