CAUTION:
Close the manifold gauge valve immediately after stopping the vacuum pump. If the valve is left
open, the vacuum pump oil will back flow into the refrigeration cycle and cause a decrease in the
efficiency of the air conditioner.
8. Start the vacuum pump and let it operate for 15 min .
9. Verify that high- and low-pressure side readings of the manifold gauge are at − − − − 101 kPa {− − − − 760 mmHg,
− − − − 29.9 inHg} . Close each valve of the manifold gauge.
10. Stop the vacuum pump and wait for 5 min .
11. Inspect the high- and low-pressure side readings of the manifold gauge.
If the reading has changed, inspect for leakage and then repeat from Step 7.
If the reading has not changed, go to next step.
12. Open the valve of the refrigerant tank.
13. Weigh the refrigerant tank to charge the suitable amount of refrigerant.
(w)
RX-8 - HVAC
Page 56