Table 12: High voltage single phase PDU for Oracle Flash Storage Systems
High Voltage
kVA size
Marketing part number
Manufacturing part number
Phase
Voltage input
Number of input cords and plug type
Number of data center receptacles and
type
Maximum input current for each cord
Outlet receptacles (number/type)
Outlet groups for each PDU
PDU power cord length
Table 13: High voltage three-phase PDU for Oracle Flash Storage Systems
High Voltage
kVA size
Marketing part number
Manufacturing part number
Phase
Oracle FS Systems: Installation Overview
1Ph (2W + ground)
10 kVA
7104983
7051801
1
2x [2Ph. (2W+ground)] 230Vac, 50 Hz,
maximum. 25A per phase
Can be connected to Ph-N input sources in
the range of 220V – 240V AC (nominal)
2x IEC 309, 32A (Hubbell 332P6S or
equivalent)
2x IEC 309, 32A (Hubbell 332R6S or
equivalent)
25A
42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
6
2 meters (6.6 feet)
PDU power cords are 4 meters (13 feet)
long, but sections are connected for internal
routing in the rack.
3Ph (5W + ground)
15 kVA
7104980
7051915
3
26