Using The Motor Condition Monitoring Tool - Omron K6CM User Manual

Motor condition monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

9-2
Using the Motor condition monitor-
ing Tool
This section shows troubleshooting when using the Motor condition monitoring Tool.
Problems
Monitoring is impossi-
ble with the K6CM from
the Motor condition
monitoring Tool
The measured value is
displayed, but the value
at a certain time is fixed
and does not change
K6CM Motor Condition Monitoring Device User's Manual (N219)
Cause
The IP address of the computer is
automatically acquired or fixedly
set to a segment different from
the IP address of the K6CM
device.
The IP address setting of the
K6CM on the project (It can be
confirmed by [Sysmac Gateway
Console] Button) is different from
the actual IP address
The communications driver Sys-
mac Gateway between the com-
puter and the K6CM is stopped
The network port setting of Sys-
mac Gateway communications
driver can not select the LAN
card or IP address used for com-
munications.
Network port setting of Sysmac
Gateway communications driver,
the IP address used for communi-
cation is AutoIP address
(169.254.xxx.xxx).
[Start monitoring] Button is not
clicked
When using the trigger function
(external trigger or internal trig-
ger), the measurement value just
before the end is held and dis-
played after measuring and moni-
toring is over.
Possible correction
Set the IP address of the computer to
IP address of same segment as the
K6CM device.
1. Click [Delete Device] to delete the
device that you registered errone-
ously.
2. Click Add device and add the
device with the IP address that is
actually connected.
1. Click [Device setting] on the startup
screen or click the [Sysmac Gateway
Console] Button on the monitoring
screen to launch the Sysmac Gate-
way Console screen.
2. Click the Start button in the Com-
munication Service field.
1. Click [Device setting] on the startup
screen or click the [Sysmac Gateway
Console] Button on the monitoring
screen to launch the Sysmac Gate-
way Console screen.
2. In the [Network Port] field, select
the LAN card and IP address to use.
Set the IP address of the network port
setting of the Sysmac Gateway com-
munications driver to an IP address
other than AutoIP.
Click the [Start monitoring] Button.
Measure the trigger condition and
start measurement.
9 Trouble shooting
Reference
5-2-4 Motor condition
monitoring Tool IP
Address Settings on
the Computer Side
Before Starting on
page 5-19
5-4-5 Add a Device to
an Existing Project on
page 5-47
5-4-3 Procedure for
Setting IP Address
(when necessary, fur-
ther parameters) on
page 5-37
5-4-3 Procedure for
Setting IP Address
(when necessary, fur-
ther parameters) on
page 5-37
5-4-3 Procedure for
Setting IP Address
(when necessary, fur-
ther parameters) on
page 5-37
7-3-3 Start Monitoring
on page 7-7
3-2 Measuring and
Monitoring Execution
Conditions on page
3-14
9 - 3
9