Attri-
Parameter
bute ID
name
74 hex
Velocity alarm
(Critical)
75 hex
Motor tem-
perature alarm
(Warning)
76 hex
Motor tem-
perature alarm
(Critical)
77 hex
Temperature
gap alarm
(Warning)
78 hex
Temperature
gap alarm
(Critical)
 Insulation resistance type (K6CM-ISM)
Attri-
Parameter name
bute ID
6E hex
Applicable circuit
6F hex
Using inverter
K6CM Motor Condition Monitoring Device User's Manual (N219)
8 Monitoring and Setting with the EtherNet/IP
Description
Sets the velocity alarm threshold (Critical).
0 to 9999
The decimal point position follows each
input.
Sets the motor temperature alarm thresh-
old (Warning).
0 to 9999
The decimal point position follows each
input.
Sets the motor temperature alarm thresh-
old (Critical).
0 to 9999
The decimal point position follows each
input.
Sets the temperature gap alarm (Warn-
ing).
0 to 9999
The decimal point position follows each
input.
Sets the temperature gap alarm (Critical).
0 to 9999
The decimal point position follows each
input.
Description
Sets the applicable circuit.
0: Three-phase three-wire
S-phase ground
1: Three-phase four-wire
N-phase grounded load side
delta connection
Sets the presence or absence of
the inverter.
0: OFF (No inverter)
1: ON (with inverter)
(For 3 phase 4 wires N phase
ground load side delta connec-
tion, use with no inverter.If you
have an inverter you can not do
the correct measurement.)
Data
Attri-
bute
Data type
Default value
Write
UINT
45.00
(Unit: mm/s)
Write
UINT
80.0
(Unit: °C)
Write
UINT
80.0
(Unit: °C)
Write
UINT
80.0
(Unit: °C)
Write
UINT
80.0
(Unit: °C)
Data
Attri-
bute
Data type
Default value
Write
UINT
0
Write
UINT
0
8
8 - 17