Omron K6CM User Manual page 47

Motor condition monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Name
Transis-
Transistor
Warning output of comprehensive alarm.
tor Out-
Output 1
put
Transistor
Critical output of comprehensive alarm.
Output 2
Transistor
Self-diagnosis error output.
Output 3
EtherNet/IP port
Port for connecting Ethernet cable for com-
munications with Motor condition monitoring
Tool, PLC, and PC.
 Product and Network Status Indications Details
Name
MS
Module Status
NS
Network Status
K6CM Motor Condition Monitoring Device User's Manual (N219)
Color
Status
Green
Lit.
Normal status
Red
Lit.
Damaged fault (Measurement CPU data flash error, Main CPU data flash
error)
Flashing
One of the following conditions
Measurement CPU error, Main CPU error, Present value input error, Max-
imum value input error, Minimum value input error
--
Not lit.
No power supply
Green
Lit.
Tag data link or message connection established
Flashing
No tag data link or message connection established
Red
Lit.
IP address duplication status
Flashing
The connection has timed out, or the BOOTP server connection error
state
--
Not lit.
No power supply
2 Nomenclature and Functions
Meaning
In the following cases, ON
• Comprehensive alarm: normal
OFF in one of the following cases:
• Comprehensive alarm: warning or critical
• Measuring and monitoring is not started yet (only when
using the trigger function)
• Self-diagnosis error occurrence
Note : At the end of measuring and monitoring, the transistor
output 1 state is retained (only when using the trigger
function).
In the following cases, ON
• Comprehensive alarm: Normal or Warning
OFF in one of the following cases:
• Comprehensive alarm: Critical
• Measuring and monitoring is not started yet (only when
using the trigger function)
• Self-diagnosis error occurrence
Note : At the end of measuring and monitoring, the transistor
output 1 state is retained (only when using the trigger
function).
In the following cases, ON
• When Self-diagnosis error does not occur
In the following cases, OFF
• Self-diagnosis error occurrence
It is with straight / cross cable automatic discrimination func-
tion.
Operating condition
2
2 - 5

Advertisement

Table of Contents
loading

Table of Contents