4 Installation and Wiring
4-5

EtherNet/IP Wiring

This section describes the EtherNet/IP wiring of the K6CM devices.
4-5-1

EtherNet/IP Wiring

Connect the K6CM devices with the Motor condition monitoring Tool, PLC, or PC via the industrial
switching hub with the Ethernet cables.
• For 100Base-TX, use an STP (shielded twisted-pair) cable of category 5 or higher. You can use
either a straight or cross cable.
Motor condition monitoring Tool
• Initial setting
• Monitoring
EtherNet/IP
*1. When making initial
settings, connect this tool
to each motor condition
monitoring device one to
one using an Ethernet
cable without a switching
hub.
 Recommended Ethernet switches
Ethernet switches are recommended for use in environments that can be used in FA environments
and devices that can use QoS (Packet Priority Control) dedicated to EtherNet/IP.
The following are recommended items.
Manufacturer
OMRON
Cisco Systems, Inc
Contec USA, Inc.
Phoenix Contact USA
4 - 26
Industrial switching hub
*1
(e.g., W4S1)
*1
Vibration &
temperature
type
Model
W4S1-03B
Packet priority control (QoS): EtherNet/IP control data priority
Failure detection: Broadcast storm, LSI error detection,
W4S1-05B
100Base-TX, Auto negotiation
W4S1-05C
Number of ports: three for the W4S1-03B, or five each for the
W4S1-05B and W4S1-05C
Failure detection output (W4S1-05C only)
Consult the manufacturer.
http://www.cisco.com/web/JP/index.html
Consult the manufacturer.
http://www.contec.co.jp/
Consult the manufacturer.
https://www.phoenixcontact.com/online/portal/jp
PC
EtherNet/IP
Insulation
Comprehensive
resistance
current diagnosis type
type
K6CM
Motor Condition Monitoring Device
Description
K6CM Motor Condition Monitoring Device User's Manual (N219)
PLC
• Monitoring
Required settings