4 Installation and Wiring
4-3
How to Connect to the Push-In Plus
Terminal Blocks
This section describes how to connect the K6CM devices to the Push-In Plus terminal blocks.
Precautions for Safe Use
• To prevent wire materials from smoking or igniting, use the wiring materials given in the fol-
lowing table.
0.25 to 1.5 mm
• Make sure the crimp terminals for wiring are of the specified size.
• Do not insert more than one wire into each terminal insertion hole.
• Do not connect anything to terminals that are not being used.
• Do not wire anything to the release holes.
• Do not tilt or twist a flat-blade screwdriver while it is inserted into a release hole on the ter-
minal block. The terminal block may be damaged.
• Insert a flat-blade screwdriver into the release holes at an angle. The terminal block may
be damaged if you insert the screwdriver straight in.
• Do not allow the flat-blade screwdriver to fall out while it is inserted into a release hole.
• Keep wiring separate from high voltages and power lines that draw large currents. Do not
place product wiring in parallel with or in the same path as high-voltage or high-current
lines.
• Do not bend a wire past its natural bending radius or pull on it with excessive force. Doing
so may cause the wire disconnection.
• When wiring the terminals, allow some leeway in the wire length.
Precautions for Correct Use
• When you are finished with wiring, make sure that no stranded wire comes loose.
• If you wire crossovers and connect terminal blocks in parallel, a large current will flow. Make
sure that the current does not exceed 10 A.
• The terminal block may be damaged if the recommended tool is not used. Use the recom-
mended flat-blade screwdriver to operate the release holes.
4-3-1

Type of terminal block

The following wiring terminals of the K6CM devices are all Push-In Plus terminals.
• Input wiring (sensor input, power supply input, external trigger input)
• Output wiring (transistor output)
4 - 14
Recommended Wire
2
(AWG24 to AWG16)
Stripping length
(Without Ferrules)
8 mm
K6CM Motor Condition Monitoring Device User's Manual (N219)