Omron K6CM User Manual page 31

Motor condition monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Item
Output
Output form
Functions
Output rating
EtherNet/IP
Connected device
Communications
type
*1. Judgment of comprehensive alarm as a device:
• Comprehensive alarm threshold setting (Warning) setting: A state in which "Critical" does not exist in the
measurement value and "Warning" exists even in even one.
• Threshold (Critical) setting for comprehensive alarm: A state in which at least one of the measurement val-
ues has "Critical".
Ratings
Item
Power supply voltage
Allowable operating voltage
range
Power supply frequency
range
Power consumption
Startup time at power ON
LCD display
Indicators
External trigger input
(excluding the K6CM-ISM)
Transistor output
K6CM Motor Condition Monitoring Device User's Manual (N219)
Transistor output (normally closed)
The following 3 points
• Transistor output 1: Threshold (Warning) setting output of comprehensive alarm
(Alarm occurrence: OFF, Alarm non-occurrence: ON)
• Transistor output 2: Threshold (Critical) setting output of comprehensive alarm (Alarm
occurrence: OFF, Alarm non-occurrence: ON)
• Transistor output 3: Self-diagnosis error output
(Self-diagnosis error occurrence: OFF, Self-diagnosis error not occurring: ON)
Contact configuration: NPN open collector
Rated voltage: 24 VDC
Maximum current: 50 mA
Motor condition monitoring Tool, or EtherNet/IP compatible equipment such as PC, PLC
• CIP message communication: reception of CIP command
• Tag data link: Output only
K6CM-MA: 100 to 240 VAC, 50/60 Hz (Alternating current)
K6CM-MD: 24 VAC, 50/60 Hz, 24 VDC (Both direct and alternating current)
85% to 110% of the rated power supply voltage
45 to 65 Hz
K6CM-VBM
24 VAC/24 VDC: 3.8 VA/2.1W max.
100 to 240 VAC: 7.1 VA max.
K6CM-ISM
24 VAC/24 VDC: 3.7 VA/2.0W max.
100 to 240 VAC: 6.2 VA max.
K6CM-CIM
24 VAC/24 VDC: 3.1 VA/1.6W max.
100 to 240 VAC: 6.0 VA max.
10 s or less
Note : This is the time from power-ON until the measuring and monitoring start or "- - - -" is dis-
played.
After that, the measurement value is displayed after the sampling time has elapsed.
7 segment digital display and single light display Character height 14 mm
MS: red / green, NS: red / green, alarm bar: green / orange / red
No-voltage contact and open collector are possible.
Short circuit: Residual voltage 1.5 V or less
Open: Leakage current 0.1 mA or less
Short circuit current: approx. 7 mA
Minimum trigger time: 0.1 s
Contact configuration: NPN open collector (normally closed)
Rated voltage: 24 VDC (maximum voltage: DC 26.4 V)
Maximum current: 50 mA
Specifications
Specifications
1 Overview
1
1 - 11

Advertisement

Table of Contents
loading

Table of Contents