Inverter Operation: 100%
Example of actual measurement:
Initially measured value of the
degradation level is "51".
K6CM Motor Condition Monitoring Device User's Manual (N219)
3 Mechanism of Measuring and Monitoring of the K6CM Devices
Example:
The degradation level measured at the beg-
ging of use is "51" due to the influence of
inverter control. However, it is not abnormal.
In this case of using an inverter, this initially
measured value "51" should be added to the
alarm threshold.
Therefore, alarm threshold of degradation
level (Warning) should be "71" that is added
"20" to this value. One of degradation level
(Critical) should be "101" that is added "50" to
this value. Perform trend monitoring after
these settings.