4 Installation and Wiring
4-2-6

Installation and Connection of Dedicated CT

Dedicated CT for Comprehensive current diagnosis type (K6CM-CIM) must be used always with the
dedicated CT supplied cable.
Note Do not extend the dedicated CT supplied cable. An extended cable for it does not satisfy the safety standards.
Wiring of the dedicated CT
1
Remove the secondary terminal cover on the bottom of the dedicated CT.
Because the cover is stopped with two claws on the side, float the claws with your fingers and
remove it.
2
Connect the included cable (K6CM-CICB) for the dedicated CT to the secondary side terminal
under the cover.
Screw the round terminal on the CT side of the cable to the secondary side terminal with a screwdriver.
Be careful not to make a mistake as there are L (load side) and K (power supply side) for the terminals.
3
Close the secondary terminal cover.
Close the cover in the reverse order of removal.
Be sure to close the electrode of the secondary side terminal, since it may cause electric shock
when you touch it.
4 - 12
Dedicated CT
Dedicated CT supplied cable
Secondary
remove
terminal cover
Dedicated CT provided cable (CT side)
Below the secondary terminal cover
CT split type
hook
Secondary
side terminal
K6CM Motor Condition Monitoring Device User's Manual (N219)