Omron K6CM User Manual page 190

Motor condition monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

8 Monitoring and Setting with the EtherNet/IP
Attri-
Parameter name
bute ID
70 hex
Inverter special mea-
surement
71 hex
Insulation resistance
alarm (Warning)
72 hex
Insulation resistance
alarm (Critical)
 Comprehensive current diagnosis type (K6CM-CIM)
Attri-
Parameter
bute ID
name
6E hex
Current range
6F hex
Reserved.
70 hex
Reserved.
71 hex
Current alarm
(Warning)
72 hex
Current alarm
(Critical)
73 hex
Degradation
level alarm
(Warning)
74 hex
Degradation
level alarm
(Critical)
8 - 18
Description
Sets the Inverter Special measure-
ment.
0: OFF
1: ON
Special calculation to do when
inverter frequency and commercial
frequency are close.
Note : With or without inverter =
"with inverter" only valid
For how to use this function, refer
to the Wiring Diagram of the Insu-
lation Resistance Type
(K6CM-ISM) on page 4-20 in 4-4-1
I/O wiring on page 4-19.
Sets the insulation resistance
alarm threshold (Warning).
0.000 to 1.000
Sets the insulation resistance
alarm threshold (Critical)).
0.000 to 1.000
Description
Sets the current range.
0: 5 A
1: 25 A
2: 100 A
3: 200 A
4: 400 A
5: 600 A
Reserved.
Reserved.
Sets the current alarm (Warning).
0 to 9999
The decimal point position follows each
input.
Sets the current alarm (Critical).
0 to 9999
The decimal point position follows each
input.
Sets the degradation level alarm (Warn-
ing).
0 to 999
Sets the degradation level alarm (Critical).
0 to 999
K6CM Motor Condition Monitoring Device User's Manual (N219)
Data
Attri-
bute
Data type
Default value
Write
UINT
0
Write
UINT
0.8
(Unit: MΩ)
Write
UINT
0.4
(Unit: MΩ)
Data
Attri-
bute
Data type
Default value
Write
UINT
3
Write
UINT
0
Write
UINT
0
Write
UINT
200.0
(Unit: A)
Write
UINT
200.0
(Unit: A)
Write
UINT
30
Write
UINT
50

Advertisement