Observe these guidelines when the 2094-AL09 or 2094-BL02 LIM module is
used in the Bulletin 2094 system and mounted left of the IAM module:
• The clean zone (C) is to the right and beneath the Bulletin 2094 system
(gray wireway).
• The dirty zone (D) is to the left and above the Bulletin 2094 system, and
above and below the LIM module (black wireway).
• The very dirty zone (VD) is limited to where the LIM module VAC
output jumpers over to the IAM module. Shielded cable is required only
if the very dirty cables enter a wireway.
• The Sercos fiber-optic cables are immune to electrical noise, but due to
their delicate nature, route them in the clean zone.
This layout is preferred due to the reduced size of the very dirty zone.
Figure 14 - Noise Zones (LIM mounted left of IAM module)
Dirty Wireway
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
D
D
Line Interface Module
D
Route 24V DC I/O
shielded cable.
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway.
(2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Plan the Kinetix 6000 Drive System Installation
(1)
Motor Power Cables
D
VD
C
D
Route encoder/analog/registration
Chapter 2
Clean Wireway
C
Fiber-optic Cable
(2)
No sensitive
equipment within
150 mm (6.0 in.).
Kinetix 6000
System
C
(1)
I/O
and Feedback Cables
shielded cables.
41