Allen-Bradley 2094-AC05-MP5 User Manual page 168

Multi-axis servo drives 2094-acxx-mxx-s; 2094-bcxx-mxx-s; 2094-amxx-s; 2094-bmxx-s; 2094-acxx-mxx; 2094-bcxx-mxx; 2094-amxx; 2094-bmxx; 2094-bsp2; 2094-prf; 2094-sepm-b24-s;
Table of Contents

Advertisement

Chapter 7
Troubleshooting the Kinetix 6000 Drive System
Table 102 - Seven-segment Status Indicator Error Codes (continued)
Error
Fault Message - Logix
Code
Designer (HIM)
BusUndervoltage Fault
E09
(Bus Undervoltage)
DriveOvervoltage Fault
E10
(Bus Overvoltage)
MotFeedbackFault
E11
(Illegal Hall State)
Softovertravel Fault
E16
(+/- Software Overtravel)
OverSpeedFault
E18
(Overspeed Fault)
PositionErrorFault
E19
(Follow Error)
MotFeedbackFault
E20
(Mtr Fdbk AQB)
AuxFeedbackFault
E21
(Aux Feedback Comm)
MotFeedbackFault
E30
(Motor Feedback Comm)
E31
DriveHardFault
GroundShortFault
E34
(Ground Fault)
168
Anomaly or Symptom
Potential Cause
With three-phase power
present, the DC bus voltage is
• DC bus voltage for 460V system is below
below limits.
275V
• DC bus voltage for 230V system is below
DC bus voltage fell below the
137V
undervoltage limit while an
axis on the follower power rail
was enabled.
Excessive regeneration of power.
When the motor is driven by an external
mechanical power source, it can regenerate too
The DC bus voltage is above
much peak energy through the drive power
limits.
supply. The system faults to save itself from an
overload.
• DC bus voltage for 460V system is over 820V
• DC bus voltage for 230V system is over 410V
State of Hall feedback inputs
Improper connections.
is incorrect.
Axis position exceeded maximum software setting.
Motor speed has exceeded 150% of maximum rated speed. The 100% trip point is
dictated by the lesser of the user velocity limits or the motor rated base speed.
Position error limit was exceeded.
The motor encoder encountered an illegal
Motor Encoder State Error
transition.
Communication was not established with an intelligent encoder.
Communication was not established with an intelligent encoder.
Excessive motor shaft movement during power up, Sercos ring phase-up, or after
a fault reset.
Wiring error.
Motor internal ground short.
Excessive ground current in
Internal malfunction.
the converter was detected.
Grounded control power terminal
(applies to 230V systems only)
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Possible Resolution
• Verify voltage level of the incoming AC power.
• Check AC power source for glitches or line drop.
• Install an uninterruptible power supply (UPS)
on your AC input.
Disable follower axis before removing power.
• Change the deceleration or motion profile.
• Use a larger system (motor and Kinetix 6000
drive).
• Install shunt module.
Verify input is within specifications.
• Verify the Hall wiring at the MF connector on
the IAM/AM module.
• Verify 5V power supply to the encoder.
• Verify motion profile.
• Verify overtravel settings are appropriate.
• Check cables for noise.
• Check tuning.
• Increase the feed forward gain.
• Increase following error limit or time.
• Check position loop tuning.
• Verify sizing of system.
• Verify mechanical integrity of system within
specification limits.
• Use shielded cables with twisted pair wires.
• Route the feedback away from potential noise
sources.
• Check the system grounds.
• Replace the motor/encoder.
Verify auxiliary encoder wiring.
• Verify motor selection.
• Verify the motor supports automatic
identification.
• Verify motor encoder wiring.
Make sure there is no motor shaft movement
during power up, Sercos ring phase-up, or during a
fault reset.
• Check motor power wiring.
• Check input power wiring.
Replace motor.
Disconnect motor power cable from drive and
enable drive with current limit set to 0. If fault
clears, then a wiring error or motor internal
anomaly exists. If fault remains, call your sales
representative.
• Remove ground from control power input.
• Source control power from three-phase input
power (refer to diagram on
page
192).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents