Chapter 6
Configure and Start the Kinetix 6000 Drive System
If
Your test completes successfully, this dialog box opens.
Your test failed, this dialog box opens.
(1) The hardware enable input for IDM units is on the IPIM module.
158
IMPORTANT Hardware Enable input for IDM units is on the IPIM module.
6. Click the desired test (Marker/Feedback/Command & Feedback) to
verify connections.
The Online Command dialog box opens. Follow the on-screen test
instructions. When the test completes, the Command Status changes
from Executing to Command Complete.
7. Click OK.
The Online Command - Apply Test dialog box opens (Feedback and
Command & Feedback tests only). When the test completes, the
Command Status changes from Executing to Command Complete.
8. Click OK.
9. Determine if your test completed successfully.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Then
1. Click OK.
(1)
2. Remove Hardware Enable Input
signal (IOD-2).
3. Go to Tune the Axes on
page
159.
1. Click OK.
2. Verify the Bus status indicator turned solid green during the test.
3. Verify that the Hardware Enable Input
to the axis you are testing.
4. Verify conversion constant entered in the Conversion tab.
5. Return to main
step 6
and run the test again.