Diagnostics
4.1 Diagnostics via LEDs
4.1.4.5

Terminal Module TM41

Table 4- 50
Meaning of the LEDs on the Terminal Module TM41
LED
Color
READY
-
Green
Orange
Red
Green/red
Green/
orange
or
Red/
orange
Z pulses
Red
Green
The parameters for activating component recognition using LEDs can be taken from the following reference:
1)
Reference: /LH1/ SINAMICS S120/S150 List Manual
338
Status
Off
The electronics power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation. Cyclic DRIVE-CLiQ
light
communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
This component has at least one fault.
light
Note:
The LED is activated irrespective of whether the corre-
sponding messages have been reconfigured.
Flashing
Firmware is being downloaded.
light 0.5 Hz
Flashing
Firmware download is complete. The system waits for
light 2 Hz
POWER ON.
Flashing
Component recognition via LED is activated
light
Note:
Both options depend on the LED status when component
recognition is activated.
Off
The zero mark was found and the system waits for the
zero mark output.
OR
The component is switched off.
Continuous
The zero mark has not been released, or the zero mark
light
search is running.
Continuous
The system stops at the zero mark.
light
Flashing
The zero mark is output at each virtual revolution.
light
Description, cause
.
1)
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Remedy
Remove and
acknowledge the fault.
Carry out a POWER
ON.