Siemens Sinamics s120 Commissioning Manual page 41

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

Pulse frequencies and current controller sampling times:
● The current controller sampling times of the drives and infeeds must be synchronous to
the set pulse frequency of the power unit (see also p1800 in the SINAMICS S120/S150
Lists Manual). Any increase in the pulse frequency requires a reduction in the sampling
times and increases the derating in the power unit.
Line Modules
● For Active Line Modules (ALM) and Smart Line Modules (SLM) in booksize format the
only current controller sampling time which can be set is 125 µs or 250 µs.
● For Active Line Modules (ALM) and Smart Line Modules (SLM) in chassis format the
permitted current controller sampling time depends on the relevant module. The current
controller sampling time can either only be set to 250 µs or the current controller sampling
time selected can be 400 µs or 375 µs (375 µs for p0092 = 1).
● For Basic Line Modules (BLM) the only current controller sampling time which can be set
is 2000 µs (chassis format) or 250 µs (booksize format).
Motor Modules
● For Single Motor Modules in booksize format, a current controller sampling time of
minimum 31.25 µs can be set (31.25 µs ≤ p0115[0] ≤ 500 µs).
● For Double Motor Modules in booksize format, a current controller sampling time of
minimum 62.5 µs can be set (62.5 µs ≤ p0115[0] ≤ 500 µs).
● For Motor Modules in chassis format, a current controller sampling time of minimum 125
µs can be set (125 µs ≤ p0115[0] ≤ 500 µs).
● For Motor Modules in blocksize format, a current controller sampling time of 62.5 µs,
125 µs, 250 µs or 500 µs can be set (only pulse frequencies in multiples of 2 kHz are
permissible).
For PM240-2 FS D-F the minimum current controller sampling time is 125 µs.
● For the HLA module, a current controller sampling time of minimum 62.5 µs can be set
(62.5 µs ≤ p0115[0] ≤ 250 µs).
Servo control / HLA control
● A current controller sampling time between 31.25 µs and 250 µs can be set for servo
drives (31.25 µs ≤ p0115[0] ≤ 250 µs).
● For HLA drives, a current controller sampling time between 62.5 µs and 250 µs can be
set (62.5 µs ≤ p0115[0] ≤ 250 µs).
● The fastest sampling time for a drive object in servo control or HLA is as follows:
– T
– T
– T
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
= 31.25 µs: Exactly one drive object in servo control
i
= 62.5 µs: Max. three drive objects in servo control or HLA
i
= 125 µs: Max. six drive objects in servo control or HLA
i
2.5 System rules, sampling times and DRIVE-CLiQ wiring
Preparation for commissioning
41

Advertisement

Table of Contents
loading

Table of Contents