Commissioning
3.3 STARTER commissioning tool
12.Close the "Edit Ethernet node" window.
13.Activate the option button in front of the detected drive unit and click the "Accept" button.
The SINAMICS drive with CBE20 is transferred as a drive object into the project tree. You
can now continue to configure the drive object.
14.Click the "Connect to target system" button and then call the menu "Target system >
Load > To target device", to load the project to the Control Unit memory card.
The IP address and device name are stored non-volatile on the memory card of the
Control Unit.
114
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5