Description Of The Led States Of A Cu310-2 - Siemens Sinamics s120 Commissioning Manual

With starter
Hide thumbs Also See for Sinamics s120:
Table of Contents

Advertisement

LED
Color
Red
OPT
(OPTION)
Green
Red
RDY and DP
Red
RDY and OPT Orange
4.1.1.2

Description of the LED states of a CU310-2

There are four LEDs on the front panel of the CU310-2 DP housing.
Table 4- 8
RDY
COM
OUT > 5V
MOD
The various LEDs are switched either on or off as the Control Unit powers up (depending on
the phase that the system is currently in). When switched on, the color of the LEDs shows
the status of the corresponding power-up phase.
In the event of a fault, power up will be ended in the corresponding phase. The LEDs that
are switched on retain their colors so that the fault can be determined on the basis of the
combination of the color LEDs that are lit and unlit.
All the LEDs go out briefly if the CU310-2 DP has powered up without fault. The system is
ready for operation when the LED "RDY" is permanently green.
All the LEDs are controlled by the loaded software during operation.
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
State
Description, cause
Flashing
Bus fault,
light
incorrect parameter assignment/configuration.
0.5 Hz
Flashing
Cyclic bus communication has been interrupted or
light
could not be established.
2 Hz
Off
The electronics power supply is missing or outside
the permissible tolerance range.
Component is not ready.
Option board not installed or no associated drive
object has been created.
Continu-
Option board is ready.
ous light
Flashing
Depends on the option board used.
light
0.5 Hz
Flashing
This component has at least one fault.
light
The Option Board is not ready (e.g. after switching
2 Hz
on).
Flashing
Bus fault - communication has been interrupted.
light
2 Hz
Flashing
Firmware update in progress for connected Option
light
Board CBE20.
0.5 Hz
LEDs
Ready
Option Board
Encoder current supply > 5 V (TTL/HTL)
Operating mode (reserved)
Diagnostics
4.1 Diagnostics via LEDs
Remedy
Adapt configuration between
controller and devices
Remove the fault
Check power supply and/or
component
Remove the fault and
acknowledge
Remove the fault