Commissioning
3.3 STARTER commissioning tool
3.3.1.3
BICO interconnection procedure in STARTER
You can parameterize the drive settings in the OFFLINE mode via STARTER by means of
BICO interconnection. Parameterization can be carried out via the following means:
● Expert list
● Graphical screen interface
The steps described below explain the general BICO interconnection procedure in the
STARTER commissioning tool.
BICO interconnection in the expert list
When carrying out BICO interconnection via the expert list, proceed as follows:
You want to interconnect parameter p0840 of the control word with parameter r8890[0], for
example.
1. In the project navigator, select for example "Drive_1", and call the expert list via the
shortcut menu "Expert list".
2. Search for parameter p0840.
Image 3-2
86
Parameters in the expert list
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5