Parallel connection of Motor Modules in the STARTER commissioning tool
Image 3-35
Select the number of Motor Modules connected in parallel in the drop-down list, "Number of
parallel modules" (max. 4 Motor Modules).
Note
For the parallel connection, operation is released for a maximum of 8 power units (max. 4
Motor Modules and max. 4 Line Modules).
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5
Example of a parallel connection of 3 Motor Modules (chassis format, in vector control)
3.10 Commissioning of power units connected in parallel
Commissioning