Commissioning
3.3 STARTER commissioning tool
3.3.5

Activating online operation: STARTER via PROFINET IO

Online operation with PROFINET IO is implemented using TCP/IP.
Preconditions
● STARTER as of version 4.1.5
● PROFINET-confom CU3xx PN
● CU32x with CBE20
STARTER via PROFINET IO (example)
Image 3-19
Establishing online operation with PROFINET
1. Assign the PG/PC a fixed, free IP address. In our example, we selected 169.254.11.1,
based on the factory setting of the integrated Ethernet interface X127 (169.254.11.22).
Set the subnet mask to 255.255.0.0.
Note
Ethernet interface X127 is intended for commissioning and diagnostics.
Do not use this interface for other purposes and ensure that X127 is always accessible
(e.g. for service).
2. Make the settings in the STARTER commissioning tool.
3. Select online operation in the STARTER commissioning tool.
108
Connecting the PG/PC to the target device via PROFINET (example)
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5