Preparation for commissioning
2.5 System rules, sampling times and DRIVE-CLiQ wiring
The following applies for the CU Link and the CX32 and NX10/NX15 Control Units:
● In a topology with CU Link, the SINUMERIK NCU is DRIVE-CLiQ master for the NX and
the SIMOTION D4xx is master for the CX32.
● The CX32 or NX10/NX15 Control Units are master for the subordinate components.
● The connection to the Control Unit is obtained from the PROFIBUS address of the CX/NX
(10 → X100, 11 → X101, 12 → X102, 13 → X103, 14 → X104, 15 → X105).
● It is not permitted to combine SIMOTION Master Control Units and SINUMERIK Slave
Control Units.
● It is not permitted to combine SINUMERIK Master Control Units and SIMOTION Slave
Control Units.
2.5.4.2

Recommended interconnection rules

The following recommended rules should be observed for the DRIVE-CLiQ wiring:
General
● The following applies to all DRIVE-CLiQ components with the exception of the Control
Unit: The DRIVE-CLiQ sockets Xx00 are DRIVE-CLiQ inputs (Uplink), the other DRIVE-
CLiQ sockets are outputs (Downlink).
– The DRIVE-CLiQ cable from the Control Unit should be connected to DRIVE-CLiQ
– The DRIVE-CLiQ connections between the power units should each be connected
Line Modules
● An individual Line Module should be connected directly to the Control Unit (recommended
DRIVE-CLiQ socket: X100).
– Several Line Modules should be connected in series.
Motor Modules
● No more than 6 Motor Modules should be connected to a DRIVE-CLiQ line on the Control
Unit (including with vector, V/f control).
● Motor Modules should be connected directly to the Control Unit in vector control.
– If the DRIVE-CLiQ socket X100 is already assigned to a Line Module, the DRIVE-
– Several Motor Modules should be connected in a line.
– If there is already a Line Module present at X100, the Motor Module should be
– Several Motor Modules should be connected in a line.
50
socket X200 on the first booksize power unit or X400 on the first chassis power unit.
from the DRIVE-CLiQ sockets X201 to X200 and/or X401 to X400 on the follow-on
component.
CLiQ socket X101 should be used.
connected in line to socket X201 of the Line Module.
STARTER Commissioning Manual
Commissioning Manual, (IH1), 07/2016, 6SL3097-4AF00-0BP5